Temprite adds new vertical suction accumulators to its product lines for refrigeration systems. A suction accumulator is used to prevent a damaging overflow of liquid refrigerant and oil from going back to the compressor. It does this by metering the rate at which liquid refrigerant and oil are returned to the compressor, by heating the liquid to a gas. Each suction accumulator has one ODS inlet and one ODS outlet connection, and a threaded female pipe port. The female port is for the customer to install an over-pressure safety-relief device of his choosing.
Suction Accumulators
Temprite Vertical Suction Accumulators accommodate nearly all refrigerants: (See chart)
The two smaller Vertical Suction Accumulators (Model’s SA4-10 and SA6-15) have a bottom mounting stud, and are UL listed. The two larger Vertical Suction Accumulators (Model’s SA8-20 and SA10-25) are designed, fabricated, and stamped per ASME Section VIII. These two larger models are installed with fixed mounting feet.
Part # | Model | Inlet/ Outlet |
A. Relief Port |
B. Dia. |
C. Height |
D. Height of Cylinder |
Internal Volume |
MAWP | MDMT | Code of Constr. |
96104100 | SA4-10 | 7/8″ ODS* | 1/8″ FPT* | 102 mm 4″ |
281 mm 11-1/16″ |
254 mm 10″ |
1.84 L .49 gal |
44.8 bar @ 160°C 650 psig @ 320°F |
0°C @ 44.8 bar 32°F @ 650 psig |
UL |
96106150 | SA6-15 | 1-1/8″ ODS* | 1/4″ FPT* | 152 mm 6″ |
385 mm 15-1/8″ |
357 mm 14-1/16″ |
5.45 L 1.44 gal |
44.8 bar @ 160°C 650 psig@ 320°F |
0°C @ 44.8 bar 32°F @ 650 psig |
UL |
96108200 | SA8-20 | 2-1/8″ ODS* | 1/2″ FPT* | 219 mm 8-5/8″ |
575 mm 22-5/8″ |
527 mm 20-3/4″ |
15.50 L 4.09 gal |
41.4 bar @ 162.8°C 600 psig @ 325°F |
-28.9°C @ 41.4 bar -20°F @ 600 psig |
ASME UM |
96110250 | SA10-25 | 3-1/8″ ODS* | 1/2″ FPT* | 273 mm 10-3/4″ |
703 mm 27-11/16″ |
639 mm 25-1/8″ |
30.85 L 8.15 gal |
41.4 bar @ 162.8°C 600 psig @ 325°F |
-28.9°C @ 41.4 bar -20°F @ 600 psig |
ASME UM |
*FPT = Female Pipe Thread, ODS = Outside Diameter Solder
Pump Down Capacity | ||||
Model | R22 | R410A | R134a | R404A |
SA4-10 | 1.9 kg 4.3 lb |
1.7 kg 3.8 lb |
2.0 kg 4.3 lb |
1.7 kg 3.7 lbs |
SA6-15 | 5.7 kg 12.6 lb |
5.0 kg 11.1 lb |
5.8 kg 12.7 lb |
4.9 kg 10.9 lb |
SA8-20 | 16.2 kg 35.7 lb |
14.2 kg 31.4 lb |
16.4 kg 36.2 lb |
14.1 kg 31.1 lb |
SA10-25 | 32.3 kg 71.1 lb |
28.4 kg 62.7 lb |
32.7 kg 72.1 lb |
28.1 kg 61.9 lb |
All pump-down capacities are calculated using 90% of receiver volume at 90°F.